400 KV - 120KN composite long rod insulator
Rated Voltage: 400 kV
Specified Mechnical Load: 120 kN
Standard: IEC
Parameter | Unit | Value | |
---|---|---|---|
Model |
|
FXB4-400/120SB
|
FXB3-400/120SB
|
Country or original |
|
China
|
China
|
Max. voltage |
kV
|
425
|
425
|
Standard |
|
IEC
|
IEC
|
Material |
|
HTV Silicone Rubber
|
HTV Silicone Rubber
|
Core rod diameter |
mm
|
18
|
18
|
Minimum creepage Line |
mm
|
13020
|
13020
|
Specified Mechanical Load(SML) |
kN
|
120
|
60
|
Power frequency withstand voltage, dry |
kV
|
635
|
625
|
Power frequency flashover voltage, dry |
kV
|
600
|
870
|
Power frequency withstand voltage, wet |
kV
|
400
|
600
|
Power frequency flashover voltage, wet |
kV
|
505
|
755
|
Lightning impulse withstand voltage, positive |
kV
|
750
|
1200
|
Lightning impulse falshover voltage, positive |
kV
|
950
|
1455
|
Lightning impulse withstand voltage,negative |
kV
|
780
|
1250
|
Lightning impulse falshover voltage,negative |
kV
|
1035
|
1530
|
Maximum RIV at 1M Hz |
dB
|
40
|
40
|
Minimum dry arcing distance |
mm
|
1520
|
2300
|